Seat leakage

These valves are no shut-off elements ensuring a tight closing of the valve. In accordance with DIN EN 60534-4 and/or ANSI FCI 70-2 they may feature a leakage rate in closed position in compliance with the leakage classes II – V:

Want more information on cooling tower float assembly? Feel free to contact us.

Leakage class II (metal sealing double seat cone) = 0.5% Kvs value
Leakage class III (metal sealing cone) = 0.1 % Kvs value
Leakage class IV (PTFE seal cone) = 0.01 % Kvs value
Leakage class V (soft seal cone) = 1.8 x 10-5 x Δp x D* [l/h]
*D=seat diameter

For more information, please visit fill in cooling tower.

During operation, however, solid particles (e.g. sand, welding nuggets etc.) often cause damage and seat leakage. Any low leakage requirement must be expressly specified when ordering. Valve leakage can be considerably reduced by special measures such as lapping the valve seat, using special cone seals and increasing the valve closing force by changing the lever geometry or increasing the size of the float.